Meets Approved Document B 6 checks
- 15.14b Text letter height at least 50mm 60.0mm
- 15.14b Floor numeral height at least 75mm 100.0mm
- 15.15 Wording takes the form "Floor X" Floor 1
- layout Wording fits on the sign
- 15.14b Sans serif typeface Arimo Bold
- 15.14e Contrasting background, legible in low light Photoluminescent text and border on green
Mount signs 1.7m–2.0m above floor level, at the same height on every floor (15.14d), where they can be seen from the top step of the firefighting stair (15.14c).
Fix the flat sign directly below the floor sign, with its top edge no more than 50mm below the floor sign's bottom edge (15.16a).